Maintenance
The care of a fan unit should be carried out by routine inspection performed according to a definite schedule. The timing intervals required are dependant upon the working conditions and environment of the fan and the demands of operational reliability. The latter should have been a major requirement in the fan specification and in the criteria for evaluation of competing products.
Good maintenance practices cannot reverse deficiencies of fan selection. Some fans may require attention every day; topping up oil reservoirs for example. Periods exceeding one week are inadvisable, especially in the case of fans in distant fanhouses and lacking alarm systems. Observations such as listening and feeling for vibrations, and checks on pressure, flow and power consumption should be performed with every inspection in addition to the checking of gaskets and shaft seals. More detailed investigation should, of course, be undertaken if deviations from normal operation are noted.
If several fans are included in the system, the starting sequence should be adjusted with the lag-lead switch so that the running time is divided between all the units. Automatic and alarm devices should also be regularly tested.
In the absence of any specific instructions, the recommendations given in Section 18.5.3 should be followed.
In the selection of fans and the planning of their systems, it is necessary to take into account all aspects of maintenance. The assessment of a particular fan should be based on technical grounds connected with maintenance such as ease of dismantling, availability of spare parts, trade skills required and above all, a record of reliability.
The difference between routine inspection on the one hand and routine maintenance on the other is often difficult to decide. In general, it is recommended that inspection, as well as maintenance, should be carried out on a regular basis. Some form of database of faults noted and measures taken should be initiated and up-dated using PCs to allow the storage and retrieval of considerable quantities of information. Software is available which enables machinery data to be stored and individual fan service histories to be retrieved.
Under normal circumstances handling clean air, the system will need cleaning about once a year. However, with the service history of the fan and with regular routine inspections it should be possible to detect any unusual accumulation and modify these instructions accordingly.
The fan impeller should be specially checked for build up of material or dirt which may cause an imbalance, with resulting undue wear on bearings and vee belt drives. A regular maintenance programme must be established to prevent this build-up.
The rotating assembly should be inspected regularly to detect any weakening of the impeller shaft and bearings resulting from corrosion, erosion, or metal fatigue.
Do not attempt any detailed inspection of a fan unless the electrical supply has been completely disconnected. If a disconnect switch has not been provided, remove all fuses from the circuit and lock the fuse panel so that they cannot be accidentally replaced.
Maintenance in this context refers to preventive maintenance intended to reduce the number of breakdowns and the resulting unscheduled shut-downs. Attempts have been made to calculate optimum maintenance statistics for fans, but the results are uncertain and the systems are difficult to handle.
Generalisation of fan maintenance is a waste of time. Fans operate in widely differing circumstances with a vast array of materials. The best policy is to initiate a strict, very regular, routine inspection of the equipment and continue this until a pattern of equipment behaviour is apparent. At this stage, it may be possible to relax the inspection routine in some areas.
Running and maintenance instructions should be issued with every fan, if the requirements of the Machinery Directive are to be met. It is surprising how often this instruction is ignored. In the absence of any specific instructions, the following are suggested:
Every shift
When taking over plant at beginning of shift, operators should check that all bearings are cool.
Every week
Check for undue vibration. If present, stop fan at earliest opportunity, check impeller for any dirt build-up on the blades, and clean as necessary.
Every 6 months
(a) Consult motor manufacturer’s manual and carry out instructions.
(b) Examine vee belt pulleys for any chipping, tension of ropes, or
C) Check coupling alignment and condition.
Every 12 months
A) Examine impellers, fan bearings, inlet spigots/venturi. Check vee belts and pulleys or coupling element(s). If any wear, replace as necessary.
B) Check clearance at impeller, level of shaft, and general alignment. Adjust as necessary.
C) Check all H. D. bolts for tightness.
D) Refer to motor and control gear manufacturer’s maintenance instructions and act accordingly.
E) Grease-lubricated bearings should be cleaned out and grease renewed.
Refer also to all proprietary item literature and act as instructed. Lubrication should be carried out regularly according to operating conditions.
The whole question of bearing lubrication is addressed in Section 10.6. It will have been noted that the greasing intervals for ball bearings are invariably higher than for roller bearings. Nevertheless, spherical roller bearings are used particularly in many indirectly driven fans (e. g. vee belt drives) as they can resist the high radial loadings due to belt pull.
The instructions which follow do not apply to arrangement 4 and
5 fans (see Chapter 9) which should follow the motor manufacturer’s recommendations.
Bearing size (mm) |
Fan speed rev/min |
|||||
125 |
250 |
500 |
1000 |
2000 |
4000 |
|
20 |
8000 |
8000 |
6300 |
3150 |
1600 |
710 |
30 |
8000 |
8000 |
5000 |
2500 |
1250 |
560 |
40 |
8000 |
8000 |
4500 |
2240 |
1000 |
400 |
50 |
8000 |
8000 |
4000 |
1800 |
800 |
315 |
55 |
8000 |
7500 |
3550 |
1700 |
750 |
280 |
60 |
8000 |
7100 |
3150 |
1600 |
710 |
224 |
65 |
8000 |
6300 |
2800 |
1400 |
630 |
180 |
Table 18.1 Relubrication interval (operating hours) for spherical roller bearings 18.5.4.1 Split roller bearings |
Lubrication — Grease lubrication is usually satisfactory up to the likely fan maximum speeds, subject to consideration for temperature and axial loads. Greases are grouped according to maximum working temperature at the bearing. They are often water-absorbent and many contain moisture and oxidation inhibitors. Extreme pressure additives can be advantageous especially for high axial loads.
For high temperatures and speeds it is always advisable to consult the fan manufacturer.
Procedure — Apply grease as follows:
For speeds up to dn* = 20 000 the roller cage should be coated with grease and the other parts lightly covered for protection, grease weights are as shown in Table 18.2. The remaining space in the lower half cartridge should be filled with grease or the whole cartridge may be completely filled to aid sealing in wet or dirty conditions.
(*d = bearing bore (mm), n = rev/min)
For speeds over dn = 20 000, the cage and parts should be coated as above plus 25% of listed grease weight in the cartridge. Cartridges fitted with thrust bearings, which are used only up to dn = 20 000, should be completely filled with grease on assembly, including the bore of the thrust bearing.
All cartridge end bore seals should be well lubricated on assembly including the bores of the revolving triple labyrinth seals. Blanking plates should be sealed with grease or jointing compound. Swivel seatings should be lubricated: anti-scuffing compounds such as Molycote are useful.
Note: Never assemble the bearings dry or inject the grease after closing the cartridge during assembly.
Bearing bore (mm) |
Series |
||
01 |
02 |
03 |
|
50 |
0.03 |
0.05 |
|
60 |
0.05 |
0.07 |
|
65 |
0.05 |
0.07 |
|
70 |
0.06 |
0.10 |
|
80 |
0.10 |
0.15 |
|
90 |
0.12 |
0.20 |
0.40 |
100 |
0.17 |
0.30 |
0.46 |
125 |
0.20 |
0.37 |
0.46 |
Table 18.2 Recommended grease weights (kilograms) for split roller bearings Courtesy of Cooper Roller Bearings Ltd |
Routine greasing
Expansion EX bearings: One or two shots from a grease gun two or three times a year (say every 1000 hours) is usually sufficient.
Fixed GR bearings for thrust: One or two shots from a grease gun every two weeks (say every 100 hours) or longer according to duty and experience.
Recommended lubricants
All the major oil companies have greases suitable for anti-friction (ball and roller) bearings. Competition is fierce and continued improvements are being made. The bearing manufacturer should always be consulted, but those shown in Table 18.3 have been found to be satisfactory in many types of fan.
Manufacturer |
Normal temp (up to 80 0 C at brg) |
High temp (up to 120 °C at brg) |
Shell |
Alvania RA |
Darina R2 |
Mobil |
Mobilplex 47 or 48 Mobilux 2 or 3 |
Mobiltemp 1 |
Beacon 2 or 3 |
||
Spheerol AP2 or 3 |
||
LS 2 or 3 |
||
Esso |
Regal AFB 2 |
Ultra Temp |
Admax L2 or L3 |
Admax B3 |
|
Multi-purpose No 2 |
Hi temp |
|
Lupus A2 |
Bellatric 2 |
|
Rocol |
BRB 1200 |
BRB 1200 |
Table 18.3 Recommended lubricants for many types of fan |
Fixed GR bearings used for location only: Treat as expansion bearings.
Clean out and replace the grease yearly or as determined by the conditions.
Lubrication points — Cartridges are tapped ys or yA pipe according to size and series. Lubricating nipples or temporary plugs are fitted as standard. The lubricant is injected through the outer race directly to the rolling surfaces.
Grease weights — The weights given are sufficient to coat the roller bearing as described. A similar amount fills the remaining space in the lower half of the cartridge and thus three times the values given will completely fill the bearing and cartridge. All weights are approximate.
Extreme pressure greases are usually normal range and suffixed EP. High temperature greases should be checked for speeds over dn = 100 000, and replenishment intervals may be reduced.
Deviation from these standard recommendations is notified separately when required. It is essential not to overgrease as this will raise the running temperature of the bearing and may shorten its life.
Check for build-up of material on the wheel. Generally this will show up as material flaking off the fan wheel and causing an imbalance which may lead to fatigue failure of the wheel. Never allow a fan to operate if the amplitude of vibration is above the maximum safe limit. Contact the manufacturer for this information, if it is not included in maintenance instructions.
Check that cooling air to the motor has not been diverted or blocked by dirty guards or similar. Check input power: an increase may indicate that some major change has been made in the system. For other motor problems refer to motor manufacturers’ instructions.
Usually caused by improper lubrication (either “over" or “under”). In every case if the cause of the trouble is not easily seen, experienced personnel should examine the equipment before it is put back into operation. (See Section 18.5.4.)
Posted in Fans Ventilation A Practical Guide