Control Action
• Two-position (on-off) control
• Modulating control
Two-position control systems are always at full capacity or off. Best for systems with slow rate of change for controlled variable. This control is common in low cost systems, and it is relatively imprecise.
Example: Two-position control for steam valve in the steam heating coil.
Differential |
||
Valve closed on |
||
Temp, drop |
||
Valve opens |
Valve off as |
|
At Q5°F |
100° F reached |
|
Valve open on |
||
Temp, rise |
Off |
On |
95°F C35°C) |
100°F (38°C) |
Coil outlet temperature |
FIGURE 123
Control differential is difference between “on” and “off’ values of controlled variable. Operating differential is difference between extreme values of controlled variable. |
Operating differential > Control differential |
Two-position (on-off) control characteristic for steam valve in Fig. 12.2«.
Figure 2-14 Two-position (on-off) control action. |
Modulating control systems produce continuously variable output over a range. This is finer control system than two-position system, and it is typical in large HVAC systems. Figure 2-16 Modulating control action. |
Throttling range (TR) is a range of input variable over which output varies through its full range. Gain is A output per A input, and it is usually adjustable.
Proportional control is the simplest modulating action for which the controller output is a linear
Function of input:
O
Where Op is the proportional controller output, A is the controller output at zero offset, e is the error (offset), and Kp is the proportional gain constant. Set point Controlled variable (Temperature) FIGURE 12.4 |
Proportional control characteristic showing various throttling ranges and the corresponding proportional gains Kp. This characteristic is typical of a heating coil temperature controller.
Smaller TR (larger gain) =>smaller offset. Smaller TR may cause stability problems.
Stability is tendency of a system to find a steady control point after an upset. Instability is tendency for oscillations to grow.
Figure 2-18« A stable system under proportional control. |
Figure 2-186 An unstable system under proportional control. |
Proportional plus integral (PI) control is designed to eliminate offset.
Proportional + Factor °c integral of offset
O
Where Opi is the PI controller output, and Ki is the integral gain constant.
Integral term drives offset to zero.
Examples of PI control in buildings include mixed-air control, duct static pressure control, and coil controls.
Proportional plus integral plus derivative (PID) control further speeds up action of PI control May not be suitable for HVAC that usually do not require rapid control response.
Additional control rate of change of error
O
Where Opid is the PID controller output, and Kd is the derivative gain constant. Example of PID application in buildings is duct static pressure control.
Example: Comparison of P, PI, and PID controller response to input step change
Input C Load Change |
|
Error |
Time | Offset |
Error |
P | Time |
Error |
Time P + I |
P + I + D Time |
FIGURE 12.5 Performance comparison of P, PI, and PID controllers when subjected to a uniform input step change. |
Posted in Fundamentals of Heating. Ventilating, and Air-Conditioning