A psychrometric definition of this was given in section 3.4. Such a definition is not always useful—for example, in a cooler coil for sensible cooling only—and so it is worth considering another approach, in terms of the heat transfer involved, that is in some respects more informative though not precise.

Coils used for dehumidification as well as for cooling remove latent heat as well as sensible heat from the airstream. This introduces the idea of the ratio S, defined by the expression:

(a)

подпись: 
(a)

(b)

Fig. 10.5 The psychrometric relationship between sensible and total cooling load.

подпись: 
(b)
fig. 10.5 the psychrometric relationship between sensible and total cooling load.
_ sensible heat removed by the coil total heat removed by the coil

In terms of Figure 10.5 this becomes

I I 51 21 *p1 • CO I Contact factor

If the total rate of heat removal is Qt when a mass of dry air ma in kg s 1 is flowing over the cooler coil, then the sensible heat ratio S, can also be written as

(10.2)

подпись: (10.2)Mac(ti — t2)

I I 51 21 *p1 • CO I Contact factor

Where c is the humid specific heat of the airstream.

The approximate expression for sensible heat exchange given by equation (6.7) allows equation (10.2) to be re-written as

(10.3)

подпись: (10.3)Qt = 1.25 x v x (?, — t2)/S

(10.4)

подпись: (10.4)Sensible heat transfer, Qs, can also be considered in terms of the outside surface air film resistance of the coil, Ra:

Qs = (LMTD)asAl/Ra

Where At is the total external surface of the coil and LMTDas is the logarithmic mean temperature difference between the airstream and the mean coil surface temperature, /sm.

And therefore

подпись: 
and therefore
(10.5)

(10.6)

SHAPE \* MERGEFORMAT I I 51 21 *p1 • CO I Contact factor

I I 51 21 *p1 • CO I Contact factor

Ln[(/|- tsm)/(t2 — ?sm)] = (AJRa)K.25 x v)

подпись: ln[(/|- tsm)/(t2 - ?sm)] = (ajra)k.25 x v)

Whence

подпись: whence(10.7)

Since v equals Af x vf, where Af and vf are the face area and face velocity, respectively, equation (10.7) becomes

Ln[(r, — tsm)/(t2 — tsJ] = (At/Af)/(Ra x 1.25 x vf) = k

K is a constant for a given coil and face velocity but it takes no account of heat transfer through the inside of the tubes. We can now write

(^2 ~ tsm)/(ti — tsm) — exp(— k)

Reference to Figure 10.5 shows that this is the approximate definition of the by-pass factor (see equation (3.4)) and hence equals (1 — P) where (3 is the contact factor. If r is the number of rows and Ar is the total external surface area per row, At = Arxr and k becomes (ArIAf){r)l(Ral.25vf). An approximate expression for the contact factor now emerges:

Note that the contact factor is independent of the psychrometric state and the coolant temperature, provided that the mass flow ratio of air to water (usually about unity) remains fairly constant.

EXAMPLE 10.1

A four-row coil with a face velocity of 2.5 m s_I has a contact factor of 0.85. Calculate the contact factor for the following cases: (a) 3.0 m s_I and four rows, (b) 2.0 m s-1 and four rows, (c) 2.5 m s“1 and six rows, (d) 2.5 m s“1 and two rows, (e) 2.5 m s_1 and eight rows. Assume that changes in the face velocity do not significantly alter Ra.

Answer

By equation (10.8) we can calculate that

Ar 4

0.85 1 exp| i25xRllx2.5

0.15 = expl -1.28 x

AfR;

In 0.15 = (-1.28 x

Ar -1.8971

AfRa -1.28 1-482

This constant can now be used to answer the questions:

(a)|3 = 1 — exp[-1.482 x 4/(1.25 x 3.0)] = 0.79

(b)P = 1 — exp[-1.482 x 4/(1.25 X 2.0)] = 0.91

(c) P = 1 — exp[-1.482 x 6/(1.25 X 2.5)] = 0.94

(d)P = 1 — exp[-1.482 x 2/(1.25 X 2.5)] = 0.61

(e) P = 1 — exp[-1.482 x 8/(1.25 x 2.5)] = 0.98